5.4.2
8200vec287
0
Strain relief with cable clamps and screws M4 12 mm.
1
Connect the shields of the motor cables with the shield clamp and screws M5 12 mm to the shield sheet.
2
Additional strain relief with cable ties.
Use low-capacity motor cables! (Core/core ≤ 250 pF/m, core/shield ≤ 410 pF/m)
Use short motor cables if possible!
PES
HF-shield end by PE connection via shield clamp.
T1, T2
Connection terminals motor temperature monitoring with PTC thermistor or thermal contact (NC contact).
Route a separate cable (shielded) to X2/T1 and X2/T2 for the motor temperature monitoring.
Activate motor temperature monitoring with C0119 (e. g. C0119 = 1)!
Route the control and mains cables separately from the motor cable!
L
Motor connection
Cable cross-sections
Cable cross-sections U, V, W, PE
Type
E82EV753K4B
E82EV903K4B
Electrical installation
Power connections E82EV753K4B / E82EV903K4B
2
mm
70
95
EDK82EV903 DE/EN/FR 1.0
AWG
2 / 0
3 / 0