Show/Hide Bookmarks
Electrical installation
Relay output connections
5.5
Connection of relay outputs K1 and K2
Relay K1
X1.2/K11
X1.2/K12
X1.2/K14
PES
Tip!
•
A connection of the relay output is not required for operation!
•
The output message can be changed under C0008 or C0415/1.
•
The relay output can also be used to control a holding brake at a motor (see Operating
Instructions).
Relay K2
X1.3/K21
X1.3/K22
X1.3/K24
PES
Tip!
•
Operation does not require a connection of the relay output!
•
The output message can be changed under C0409.
•
The relay output can also be used to control a holding brake at a motor (see Operating
Instructions).
•
If you use a function module application I/O:
– The relay is only active with application I/O as of version E82ZAFAVx21.
30
Function
Relay position set
NC contact relay output
Relay middle contact
NO contact relay output
HF-shield end by PE connection through shield bracket.
Function
Relay position set
NC contact relay output
Relay middle contact
NO contact relay output
HF-shield end by PE connection through shield bracket.
EDK82EV903 DE/EN/FR 1.0
K11
K1
K12
K14
K21
K22
K2
K24
nc
Message
(Lenze setting)
open
TRIP
closed
TRIP
Message
(Lenze setting)
open
not assigned
closed
not assigned
X1.2
K11
K12
K14
X1.3
K21
K22
K24
nc
8200vec261
Technical data
AC 250 V/3 A
AC 250 V/3 A
DC 24 V/2 A
DC 24 V/2 A ... DC 240 V/0.22 A
DC 240 V/0 22 A
Technical data
AC 250 V/3 A
AC 250 V/3 A
DC 24 V/2 A
DC 24 V/2 A ... DC 240 V/0.22 A
DC 240 V/0 22 A
L