Wiring Of The Terminals "Controller Inhibit (Cinh)" At Operation Of Two Function Modules - Lenze Global Drive 8200 vector Instructions De Montage

Convertisseur de fréquence
Masquer les pouces Voir aussi pour Global Drive 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Show/Hide Bookmarks
6.1.1
L
Wiring of the terminals "controller inhibit (CINH)" at operation of two
function modules
Tip!
Both terminals X3/28 of the interface FIF I and FIF II are evaluated internally via an
AND-operation.
The pictures for wiring shown below serve as a circuit proposal. Considering the
AND-operation of both terminals X3/28 the wiring can be adapted to your application.
Supply of the terminals "controller inhibit (CINH)" via an external voltage source
FIF I
FIF II
E82ZAFx
+20V
GND3
GND1
X3
20
28
39 7
0
8200vec262
PES
HF shield connection by connecting the shield with a surface as large as possible to PE
0
For function modules with terminals X3/7 and X3/39: Connect X3/7 and X3/39 using a jumper
Wiring of the other terminals: ^ Mounting Instructions for the function modules
Supply of the terminals "controller inhibit (CINH)" via an external voltage source
FIF I
FIF II
E82ZAFx
+20V
GND2
GND1
X3
20
28
39 7
0
8200vec263
PES
HF shield connection by connecting the shield with a surface as large as possible to PE
0
For function modules with terminals X3/7 and X3/39: Connect X3/7 and X3/39 using a jumper
Wiring of the other terminals: ^ Mounting Instructions for the function modules
Function modules (optional)
E82ZAFS
(PT E82ZAFS100)
+5V
+20V
GND1
X3
62
9
7 20 28 E1 E2 E3 E4 39 A1 59
E82ZAFS
(PT E82ZAFS100)
+5V
+20V
GND1
X3
62
9
7 20 28 E1 E2
+
(
+12 V -0 % ...
...
+30 V +0 %, max. 120 mA)
EDK82EV903 DE/EN/FR 1.0
Mounting
GND2
X3
GND2
X3
E3 E4 39 A1 59
24 V ext.
0.5...0.6 Nm
4.4...5.3 lb-in
PES
PES
0.5...0.6 Nm
4.4...5.3 lb-in
PES
PES
33

Publicité

Table des Matières
loading

Table des Matières