Set Normal/Emergency Panel Selector Switch - Lutron GRAFIK 7000 Guide D'installation Et De Maintenance

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Power Panels (PPs):

Set Normal/Emergency Panel Selector Switch

GRAFIK 7000P processor only
The normal (non-essential)/emergency (essential) switch located on the power supply board in the
processor panel determines the operation of lighting zone controller and power panel zones on the
processor in the case of a power loss or emergency condition. (The switch is not needed if no LZCs
are being used.) Functionality of power panel zones is determined by the Normal/Emergency panel
selector switch located in each power panel. See the installation manual for each power panel for help
locating the Normal/Emergency switch.
GRAFIK 7000P processor panel
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
H H
H H
H H
H H
H H
H H
N N
N N
N N
H H
H H
0 0
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
N N
N N
N N
N N
N N
N N
I I
S S w w i i t t c c h h
P P o o s s i i t t i i o o n n
D D e e s s c c r r i i p p t t i i o o n n
Left
Normal (non-essential)
Center
Ignored
Right
Emergency (essential)
R
Notes
• If no power panels are installed, the Normal/Emergency
panel selector switch must be set to the "Ignored" position
• LZCs in emergency mode will be forced to their user-
configured emergency level. Power panels in override
mode will be forced to their user-configured override level.
Levels are set using the eLumen software.
• Contact Lutron for applications where only a subset of
LZCs should enter emergency mode during a power loss
Normal/Emergency
or emergency condition
panel selector
• A LUT-ELI-3PH is needed for each processor panel to
switch(es)
make the lighting control system UL-924 compliant. The
LUT-ELI-3PH can put the entire lighting system into
emergency/override mode due to power loss or external
contact closure. See the installation guide provided with
the LUT-ELI-3PH for complete details.
• A LUT-ELI-3PH initiating an emergency condition will
cause all lighting zone controller zones to enter emergency
mode and all power panel zones to go to their override
level if their corresponding panel selector switch is set to
Emergency (essential) and they are all wired to the same
SENSE line. This will occur regardless of the status of all
Normal panels.
O O p p e e r r a a t t i i o o n n
o o f f L L Z Z C C s s
Lighting zone controllers connected to an
LZC link on this processor panel will enter
emergency mode when power is lost to
this processor panel and all power panels
on the power panel link that are set to
Normal.
Lighting zone controllers connected to an
LZC link on this processor panel will enter
emergency mode when power is lost to
this processor panel and all power panels
on the power panel link that are set to
Normal.
Lighting zone controllers connected to an
LZC link on this processor panel will enter
emergency mode when power is lost to all
power panels on the power panel link that
are set to Normal.
Installation of GRAFIK 5000/6000/7000 System
O O p p e e r r a a t t i i o o n n
o o f f P P o o w w e e r r P P a a n n e e l l s s
Power panels connected to the
power panel link on this processor
will enter emergency mode when
power is lost to this processor panel
and all power panels on the power
panel link that are set to Normal.
This processor panel has no effect
on power panels connected to the
power panel link of this processor.
This processor panel has no effect
on power panels connected to the
power panel link of this processor.
23