User Interface (Ui) Rs485 Link Wiring - Lutron GRAFIK 7000 Guide D'installation Et De Maintenance

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

User Interface (UI)
RS485 Link Wiring
An RS485 user interface (UI) link connection, wall jack, and network interface box are required if the
processor panels are not connected via Ethernet. Follow the diagram below for wiring the UI link. The
network interface and eLumen manager will be wired and configured at commissioning time by Lutron
Services personnel.
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
H H
H H
H H
H H
H H
H H
N N
N N
N N
H H
H H
0 0
N N
T1 T1
T2 T2
N N
T3 T3
N N
T4 T4
N N
T5 T5
N N
N N
T6 T6
I I
Processor panel
(GRAFIK 7000P
with 6 links shown)
Note: Label shown
is on top of
processor assembly.
Connectors are
located on bottom
surface of
processor assembly.
Notes
• Leave terminal 2 (PWR) of the processor's UI
link unconnected
• One UI link connection is required for each
processor; multiple processors cannot be
connected to the same UI link
UI Link
1
2
3
4
D
RS485 data link from network interface to (each)
processor:
3
4
(1) #18 AWG (1.0 mm
1: Common
Link
2: No connection
terminator
(LT-1)
(1) shielded, twisted pair #18 AWG (1.0 mm
3: MUX
4: MUX
D: Drain wire in shield - keep away from ground or
circuitry. No drain termination required at wall jack.
R
Network Interface shown is an Ethernet to RS485 converter
(G7-A-NWK-E-D-4)
Wall jack shown is an NTOMX-485J-WH or NTOMX-62J
2
)
2
)
• Wiring the UI link via RS485 is not necessary if
the processor is connected via Ethernet (See
Ethernet Wiring Options for details)
• See RS485 Wiring Overview for approved cable
options and additional information when using
the RS485 wiring method
Installation of GRAFIK 5000/6000/7000 System
Network
interface
1 3 4
eLumen
manager
Ethernet data link from computer to
network interface:
3
4
(1) Category 5 UTP (unshielded,
twisted pair) cable
Link
terminator
(LT-1)
To UI link on other
GRAFIK 7000P
processors
13

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Grafik 6000Grafik 5000Grafik 7000pGrafik 6000pGrafik 5000p

Table des Matières