Ethernet Wiring Options

Copper Ethernet cabling can be used to connect a processor panel to the eLumen manager and other
processor panels. Use proper LAN (local area network) wiring practices when running and terminating
Ethernet cable. A single copper RJ45 jack is provided on the processor, which is used for
communication from processor to eLumen manager and from processor to processor (in a
multiprocessor system). The processor supports 10 or 100 BaseT operation. By default, the processor
will automatically select the fastest supported Ethernet link speed.
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
H H
H H
H H
H H
H H
H H
N N
N N
N N
H H
H H
0 0
N N
T1 T1
T2 T2
N N
T3 T3
N N
T4 T4
N N
T5 T5
N N
N N
T6 T6
I I
Processor panel
(GRAFIK 7000P
with 6 links shown)
Caution! Follow all applicable local
and national electrical codes.
Notes
• Ethernet wiring is considered PELV (Class 2:
USA); do not run in the same conduit as line
(mains) voltage wiring
• Wiring distance for any single Ethernet data link
segment is 330 ft. (100 m) max; use switches,
hubs, or the RS485 Wiring Option for longer
distances
• If all processors are connected to an eLumen
manager over Ethernet, an RS485 connection
is not required on the IP or UI links
10 Installation of GRAFIK 5000/6000/7000 System
I
. Ethernet User Interface Only Wiring Option (Direct to Computer)
Ethernet data link from one eLumen manager to one processor:
(1) Category 5 UTP (unshielded, twisted pair) crossover cable
II
. Ethernet Wiring Option for User Interface and Interprocessor
(with Network Switch or Hub)
Ethernet data link from eLumen manager to network interface to processor(s):
(1) each Category 5 UTP (unshielded, twisted pair) cable
The wall jack shown is an NT-6PS-WH with an RJ45 connector.
Network switch
or hub (provided
by others)
eLumen
manager
Wall
jack
• The Ethernet network parameters will be set
using the eLumen software; the default IP
address of each processor is 192.168.250.x,
where x is the processor's address (the
processor supports only fixed IP addresses)
• Processors communicate over the Ethernet
network using TCP/IP and multicast UDP; a
dedicated network must be used for the lighting
control system
GRAFIK
7000P
eLumen
manager
GRAFIK
7000P
R