Lighting Zone Controllers (LZCs):

Link Wiring

GRAFIK 7000P processor only
T1 T1
H H
T2 T2
H H
T3 T3
H H
T4 T4
H H
T5 T5
H H
T6 T6
H H
N N
N N
N N
H H
H H
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
0 0
N N
N N
N N
N N
N N
N N
I I
Note: Label shown is on the
cover of the processor
assembly. Connectors are
located along the bottom
edge of the processor
Processor panel
assembly.
(GRAFIK 7000P
with 6 links shown)
Link A
(typical)
1
2
3
4
D
Control wiring
Data Link
(2) #18 AWG
(1) shielded, twisted pair
2
(1.0 mm
)
#18 AWG (1.0 mm
1: Common
3: MUX
2: EMERG
4: MUX
D: Drain wire in shield
R
LZC
Small LZC panel
LZC link
LZC link
Notes
• Link terminators are not needed on LZC links
2
)
• See RS485 Wiring Overview for approved cable options
and additional information
• Links A through F can be used as either CSD or LZC links
in a GRAFIK7000 system; function is defined using eLumen
software
• It is not necessary to have the processor panel at the end
of the LZC link
Installation of GRAFIK 5000/6000/7000 System
PS SIGNAL
PS CO
M
CIR COM
WC COM
WC SIGNAL
+24V
+15V
OCC SI
G
OCC CO
M
MU
X
MU
X
LINK CO
M
EMER
G
PS SIGNAL
PS CO
M
CIR COM
WC COM
WC SIGNAL
+24V
+15V
OCC SI
G
OCC CO
M
MU
X
MU
X
LINK CO
M
EMER
G
MUX
MUX
COM
EMERG
DRAIN
Last LZC panel on link
LZC link
MUX
MUX
COM
EMERG
DRAIN