Processor Panels:

Mounting

Dimensions and Recommended Conduit Entry
Dimensions are in inches (mm)
Front View
3.25
6.475
(95)
(164)
34.75
(883)
21.27
(540)
Notes
• Reinforce wall structure, if necessary. A
processor panel weighs up to 50 lbs. (22 kg)
• Minimum clearance required:
3 in. (76 mm) minimum above
3 in. (76 mm) minimum below
3 in. (76 mm) minimum in front
Mount Processor Panel
Mount the processor panel to the wall using either
the recess (flush) or surface method shown on the
following page. Remove the subplate before
mounting processor panel enclosure. To do so,
remove and save the bottom two subplate mounting
screws and loosen the top two subplate mounting
screws. Slide the subplate toward the top of the
panel and lift out of enclosure.
6
Installation of GRAFIK 5000/6000/7000 System
14.38
(365)
Screws (4) for
hanging
subplate
22
(559)
Surface mounting
holes (4)
(152)
8.63
2.875
(219)
(73)
Right Side
View
(No PELV/Class 2: USA entry)
6.0
(152)
0.5 (13) and 0.75 (19)
conduit knockouts (18 total)
Flush
mounting
(PELV/Class 2: USA entry only)
holes (4)
0.5 (13) conduit knockouts
6
1.75
(44)
• Operating environment: 32-104 °F (0-40 °C);
relative humidity less than 90% non-condensing
• For indoor use only
Top View
1.5
Dedicated Feed Wiring
(38)
2
(51)
Bottom View
Power panel link
Interprocessor link
Control station device
(CSD) or lighting zone
controller (LZC) links
User interface link
3.875
(98)
R