Lutron GRAFIK 7000 Guide D'installation Et De Maintenance page 29

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Appendix: Using the GRAFIK7000 Processor with
Emergency Systems (continued)
Scenario 2: Single-Processor System with Lighting Zone Controller (LZC) and
Power Panel (PP) Zones
1. Set Normal/Emergency switch on at least one processor or power panel to Normal. Other panels
should have their Normal/Emergency switch set to emergency.
2. Wire the PP link connector on the processor to all power panels.
3. Wire an optional normally open (NO) switch between SENSE and COMMON.
4. All LZC and PP zones on panels set to Emergency will go to their emergency or override light levels
when switch S1 is closed or power is lost to all panels set to Normal.
GRAFIK7000 Processor
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
H H
H H
H H
H H
H H
H H
0 0
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
N N
N N
N N
N N
N N
N N
I I
1: COM
2: SENSE
#12-18 AWG
(4.0-1.0 mm
2
)
PP link
Note: Connections to
MUX and MUX
terminals required, but
not shown. Refer to
"Power Panels: Link
Wiring"
Emergency/Normal
N N
N N
N N
H H
H H
selector switch
set to
Emergency/
Essential
R
Non-Essential
S1: Emergency switch
open = normal operation
closed = emergency/override
active
1 2 3 4 D 5
Circuit selector in
power panel
Installation of GRAFIK 5000/6000/7000 System
Switch Settings
Normal/
Ignored
Emergency/
Essential
Emergency/Normal
selector switch
set to
Normal/
Non-essential
1 2 3 4 D 5
Circuit selector in
power panel
29

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Grafik 6000Grafik 5000Grafik 7000pGrafik 6000pGrafik 5000p

Table des Matières