Appendix: Using the GRAFIK7000 Processor with
Emergency Systems
The GRAFIK7000 processor offers several options to integrate with emergency systems. Follow the
example scenarios below, or contact the Lutron Technical Support Center.
Scenario 1: Single-Processor System with Lighting Zone Controller (LZC) Zones Only
1. Set Normal/Emergency switch on power supply (or supplies) to Emergency (Essential) position.
2. Wire terminal 2 (+33 V IP) on IP link to terminal 2 (SENSE) on PP link through a normally closed (NC)
switch.
3. All LZC units connected to this processor will go to their programmed emergency light level when
switch S1 is opened or power is lost to this processor panel.
GRAFIK7000 Processor
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
H H
H H
H H
H H
H H
H H
0 0
T1 T1
T2 T2
T3 T3
T4 T4
T5 T5
T6 T6
N N
N N
N N
N N
N N
N N
I I
IP link
2: +33 V IP
#12-18 AWG
S1: Emergency switch
(4.0-1.0 mm
2
)
closed = normal operation
open = emergency mode activated
28 Installation of GRAFIK 5000/6000/7000 System
Emergency/Normal
N N
N N
N N
H H
H H
selector switch
set to
Emergency/
Essential
Second power supply
(optional)
PP link
2: Sense
#12-18 AWG
(4.0-1.0 mm