Energi Savr Node
Step 3: EcoSystem link wiring
EcoSystem link wiring can be wired as NEC
Class 2. See Application Note #142 "EcoSystem Bus Class
1 and Class 2 Lighting" at www.lutron.com for more details.
Consult applicable national and local codes for compliance.
Lutron recommends using two different colors for E1 and E2.
This will prevent wiring mistakes where several link wires
are co-located. Use the following instructions for wiring the
EcoSystem link.
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker or isolator
before wiring or servicing the Energi Savr Node (ESN)
with EcoSystem unit.
Buttons and LEDs in the unit are used for troubleshooting.
If wiring is exposed when accessing buttons and LEDs, the
unit must be accessed by a certified electrician, following
local codes.
1. Turn power off.
2. Remove metal outer panel cover.
3. Remove internal plastic line voltage shield.
4. Wire the EcoSystem link from the EcoSystem terminals to all
ballasts.
5. Reinstall internal plastic line voltage shield.
6. Turn on the circuit breaker or isolator to power up. The POWER
LED lights green when powered up.
7. The ECO1 and ECO2 LEDs should flash green. See LED
Behavior tables on page 11 for more details.
8. The ESN with EcoSystem unit outputs EcoSystem-compliant
voltage levels (18 V
). Use a voltage meter to confirm this
voltage.
9. To verify functionality and wiring of EcoSystem digital link(s),
press and hold the Test button until the 'Test' LED flashes
green*. You can press the ECO1 and ECO2 buttons to cycle
each link through low-end, high-end, flashing, and off,
respectively. Upon completion, press and hold the Test button
until the 'Test' LED turns off.
10. Turn power off.
* If 'Test' LED flashes red, check all wiring.
Lutron
4
|
®
with EcoSystem
TM
Class 1 or
®
|
Installation Guide
®

EcoSystem Link Wiring

• 18 AWG to 12 AWG
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lb (0.5 N
Wire gauge
12 AWG (4.0 mm
)
2
14 AWG (2.5 mm
)
2
16 AWG (1.5 mm
)
2
18 AWG (1.0 mm
)
2
Energi Savr Node
with EcoSystem
TM
EcoSystem
Link 2
(QSN-2ECO-S only)
E1
E2
EcoSystem
Link 1
E1
E2
EcoSystem Link Wiring:
(1.0 mm
to 4.0 mm
)
2
2
m)
Maximum EcoSystem-compliant
link wire length
2200 ft (671 m)
1400 ft (427 m)
900 ft (275 m)
570 ft (175 m)