Operating Instructions
SICK-specific
Index
Name Format
(dezimal)
RP1/
16 Bit
66
FL1
unsigned
8 Bit
67
OU1
Enumeration
SP2/
16 Bit
68
FH2
unsigned
16 Bit
75
DS1
unsigned
16 Bit
76
DR1
unsigned
RP2/
16 Bit
69
FL2
unsigned
8013154/U275/2010/02/01
7. Starting, operation
Access
Range
R/W
1000-8960
0 = „Hno" : Hysteresis
mode (SP/RP) no
1 = „Hnc" : Hysteresis
mode (SP/RP) nc
R/W
2 = „Fno" : Window
mode (FH/HL) no
3 = „Fnc" : Window mode
(FH/HL) no
R/W
1040-9000
R/W
0...50000 (50s)
R/W
0...50000 (50s)
R/W
1000-8960
© SICK AG • Germany • All rights reserved • Subject to change without notice
Remark
Corresponds to the process value at which the switch is deactivated
(open, Q 0V) or to the lower limit in the window mode. In case of the
output being parametrized as „Hnc" or „Fnc" (normally closed), the logic
is inverted. The value of RP1 / FL1 shall be at least 40 units (0,5% of th
emeasuring range) lower than the value of SP1 or FH1, respectively. If this
is not the case, RP1 or FL1 are set to the nearest possible value.
„no" = „normally open",
„nc" = „normally closed".
Corresponds to the process value at which the switch is activated (closed, Q
+24V) or to the upper limit in the window mode. In case of the output being
parametrized as „Hnc" or „Fnc" (normally closed), the logic is inverted. The
value of RP2 / FL2 shall be at least 40 units (0,5% of the measuring range)
lower than the value of SP2 or FH2, respectively. If this is not the case, RP2
or FL2 are set to the nearest possible value.
Switch-on delay of Q1 in ms.
Switch-off delay of Q1 in ms.
Corresponds to the process value at which the switch is deactivated (open,
Q 0V) or to the lower limit in the window mode. In case of the output being
parametrized as „Hnc" or „Fnc" (normally closed), the logic is inverted. The
value of RP2 / FL2 shall be at least 40 units (0,5% of th emeasuring range)
lower than the value of SP2 or FH2, respectively. If this is not the case, RP2
or FL2 are set to the nearest possible value.
PBS
41