minimum venting requirements - propane
EN
3.5
LVX38-1 venting confi gurations
40'
38 1/2'
(462")
30'
V
20'
15'
10'
6'
(72")
5'
4 3/4'
(57")
2 1/2'
(30")
0'
Base of
air collar
0'
24
W415-2035 / C / 04.30.21
(PROPANE ONLY)
V+H ≤ 40 ft. H ≤ 10 ft.
(For longer vent runs, a power vent is
required).
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
For 0 elbow configurations, V is a minimum
of 6' to a maximum of 40'.
5'
3 1/4'
1 1/2'
(40")
(18")
Vertical termination only.
No horizontal termination allowed.
1-4 elbow zone
1-3 elbow zone
1-2 elbow zone
1 elbow zone
Refer to appliance
specific GPV/PVA
instructions for other
venting configurations.
10'
15'
H
25'
20'