fi nish framing - after appliance installation
EN
see-thru built out
Insulation
minimum framing
Ref
E***
N* / **
O*
P*
* Thickness of fi nishing material must be considered when constructing the framing for the protrusion (i.e. Dimen-
sions such as N, O, & P includes framing and fi nish material). If desired, side and bottom protrusions are also
permitted with 4" (10.1cm) Max. (fi nishing material not illustrated)
** This is a recommended dimension when mounting electronics above the appliance. Otherwise, it can be as
minimal as construction permits.
***Max. 21" (53.5cm).
note:
When fi nished, protrusions must never encroach inside the appliance fi nishing fl ange as this will impede
the fi tment of the barrier and safe operation. See "fi nishing" section in the installation manual.
note:
The LVX series requires a minimum enclosure height, as illustrated (dimension L), measured from the bottom of the
appliance. For temperature requirements, this area must be left unobstructed. Some venting confi gurations that re-
quire more vertical rise will require a larger enclosure to provide minimum vertical clearance between vent pipes and
combustibles.
58
W415-2035 / C / 04.30.21
N
O
E
LVX38-1
LVX50-1
Drywall
P
LVX62-1
16 3/16" (41.1cm)
14 1/4" (36.2m)
25 11/16 (65.2cm)
4" (10.1cm) Max
note:
Finish framing must be built
after appliance has been
placed in its fi nal position and
venting connected.
Option 2 illustrated (appliance
not shown)
LVX74-1