10.5 SYSTEM CONFIGURATION WITH TECHNICAL PASSWORD: 31100 (SET I/O MENU)
CONFIGURATION HOME
PAGE MENU
Visualization
ENGLISH
Viewing page of the configuration menu.
1: Set plant
2: Set inverter
3. Set inputs outputs
4: Managing Alarms
5: Electrical values
6: Software version
To enter the page of the menus press the button SB9 appears the page insert password.
Type in the user password 31100 and enter in the menu SET plants listed below.
Press SB6 –SB7 to scroll through pages of parameters.
Press SB8 –SB10 to decrease or increase the data.
Press SB9 to confirm the data.
Press SB1 to return to the HOME PAGE monitor.
Submenu SET I/O parameter
Description
3.1 Input DIG. RCTerminals: 15 - 16
Configuration of closing of digital input DIG0.
0) No change: OFF.
1) Enables remote control: RC.
2) External Fault
3) H2O leak
4) Change P.Set VAL2.
3.2 D.O. 1
Configuration of change of RL1.
0: No
1: Fault
2: Automatic
3: Manual
4: Asset value within the proportional band value
of Setpoint
5: Pump running
6: Lack Water
7: External fault
3.3 D.O. 2
Configuration of change of RL2.
0: No
1: Fault
2: Automatic
3: Manual
4: Asset value within the proportional band value
of Setpoint
5: Pump running
6: Lack Water
7: External fault
3.4 AN. OUT 1
Configuration of analog output 1.
0-Output: OFF.
1-Inverter frequency proportional output: Hz.
2-Inverter current proportional output: A
3.6 System supervisor
OFF – no supervision;
GSM - supervision by the additional gsm
Module.
3.7
GSM test message
Allows to choose any number of days to
receive a test message.
47
Field
Default
0 - 4
0: OFF
0 - 7
1: Fault
0 - 7
0: OFF
0 - 2
0: OFF
0 - 1
0:OFF
0 - 4
0:OFF