10.2 CONFIGURATION SYSTEM WITH USER PASSWORD: 20009
Visualization
1.10 Language
0: Italian
1: English
2: French
3: Russian
ENGLISH
To enter the page of the menus press the button SB9 appears the page insert password.
Type in the user password 20009 and enter in the menu SET plants listed below.
Press SB6 –SB7 to scroll through pages of parameters.
Press SB8 –SB10 to decrease or increase the data.
Press SB9 to confirm the data.
Press SB1 to return to the HOME PAGE monitor.
Description
1.10 Language
Menu language.
0) Italian
1)English
2)French
3) Russian
1.16 Load loss compensation
Automatic increase in bar of the Reference
Pressure, for switching on pumps in cascade
mode.
1.18 Periodic Speed Reduction
Set percentage of minimum speed below which
stopping of the pump supplied by the inverter
is enabled.
1.22 Minimum Speed
Set percentage of inverter speed to enable
stopping of the pumps in cascade mode.
1.23 Minimum Frequency
Inverter minimum set speed for enable the
arrest of the pump
1.26 Minimum H2O Pressure
Pressure value to be set according to
the pressure of the column of water on
delivery.
Field
0 - 3
00.0 - 01.0 bar
0 - 100 %
000 - 100 %
020 - 040 Hz
0.0 - 2.0 bar
41
Default
0
00.0 bar
085 %
070 %
025 Hz
0.5 bar