ero electronic TMS Mode D'emploi page 18

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

OUTPUT POWER OFF
OUTPUT POWER OFF
OUTPUT POWER OFF
OUTPUT POWER OFF
OUTPUT POWER OFF
The TMS allows to turn OFF manually the output
signal in order to stop the control (the instrument
will operate as an indicator only).
To turn OFF the output signal proceed as follows:
1) push and maintain the pressure on the
push-button
2) push FUNC push-button.
3) Maintaining the pressure on both push-buttons
for more than 3 seconds; the lower display will
show "OFF" and the output signal will be
inhibited.
When it is desired to come back to the normal
control, repeat the actions 1, 2 and 3; the
instrument goes automatically to the NORMAL
DISPLAY MODE.
NOTE:
NOTE: 1)The instrument memorizes the output
NOTE:
NOTE:
NOTE:
status.
2) If the output is turned OFF when the
SMART function was performing the first
part of the algorithm (LED SMRT is
flashing), the SMART function will be
aborted and when the instrument comes
back to the normal control, the SMART
function will be disabled.
If the output is turned OFF when the
SMART function was performing the
adaptive part of the algorithm (LED
SMRT is lit), the SMART function will be
stopped and, when the instrument
comes back to the normal control, the
smart function also will be activated.
HEATER BREAK DOWN ALARM
HEATER BREAK DOWN ALARM
HEATER BREAK DOWN ALARM
HEATER BREAK DOWN ALARM
HEATER BREAK DOWN ALARM
This alarm allows to verify, continuously, the
current consumed by the load driven by the main
output and generates an alarm condition when
this current is lower than a programmable
threshold.
To display the main load consumption, push the
push-button when the instrument is in
NORMAL DISPLAY MODE.
The upper display will show the measured value
while the lower display will show the main load
consumption (in Ampere) followed by the
engineering unit (A).
To come back to the normal display mode, push
the
push-button.
When an alarm condition is detected, the LED
AL2/HB will be flashing and the relay of the out 3
(alarm 2 OR heater break down alarm) will be
activated.