P10 = Alarm 2
P10 = Alarm 2
P10 = Alarm 2
P10 = Alarm 2
P10 = Alarm 2
0 = Not provided
1 = Process alarm
2 = Band alarm
3 = Deviation alarm
Alarm 2 and HBD functions are in OR condition
on the output 3 (see P16 parameter).
P11 = Alarm 2 operative mode and reset of the
P11 = Alarm 2 operative mode and reset of the
P11 = Alarm 2 operative mode and reset of the
P11 = Alarm 2 operative mode and reset of the
P11 = Alarm 2 operative mode and reset of the
HBD alarm.
HBD alarm.
HBD alarm.
HBD alarm.
HBD alarm.
Available only when P10 is different from 0 or P16
is different from OFF.
H.A = high alarm (outside band) with
automatic reset
L.A = low alarm (inside band) with automatic reset
H.L= high alarm (outside band) with manual reset
L.AL= low alarm (inside band) with manual reset
NOTE: The HBD alarm is a low alarm but it
NOTE
NOTE
NOTE
NOTE
assumes the same reset type selected for
alarm 2.
P12 = Stand by (mask) of the alarm 2
P12 = Stand by (mask) of the alarm 2
P12 = Stand by (mask) of the alarm 2
P12 = Stand by (mask) of the alarm 2
P12 = Stand by (mask) of the alarm 2
Available only when P10 is different from 0.
OFF = stand by (mask) disabled
ON = stand by (mask) enabled
For other details see P9 parameter.
P13 = Type of OFFSET applied to the
P13 = Type of OFFSET applied to the
P13 = Type of OFFSET applied to the
P13 = Type of OFFSET applied to the
P13 = Type of OFFSET applied to the
measured value
measured value
measured value
measured value
measured value
P13 = 0
the OFFSET (P14) is
constant all over the range.
P13 different from 0P13 is the application point of
the OFFSET selected by P14
parameter.
NOTE
NOTE
NOTE
NOTE
NOTE: the P13 and P14 parameters do not
modify the measuring or read-out limits of the
instrument so that when one of this limit has been
exceeded, the instrument will show an out of
range condition.
P14 = OFFSET value
P14 = OFFSET value
P14 = OFFSET value
P14 = OFFSET value
P14 = OFFSET value
When P13 = 0,
P 14 is programmable, in
engineering units, from -20% to
+ 20% of the input span (see
P1).
When P13 ≠ 0
P14 is programmable, in
engineering units, from -20% to
+ 20% of the P13 value.
NOTE: the P14 parameter can not be set lower
NOTE
NOTE
NOTE
NOTE
than -199 units.
Real
Readout.
Readout.
curve
P14
P14
Adjusted
curve
Input
P13 = 0
P15 = Threshold of the "Soft Start" function.
P15 = Threshold of the "Soft Start" function.
P15 = Threshold of the "Soft Start" function.
P15 = Threshold of the "Soft Start" function.
P15 = Threshold of the "Soft Start" function.
Threshold value, in engineering units, used by the
instrument for automatic enabling of the "soft
start" function (timed output power limiting).
At instrument start up, if the measured value is
lower than the programmed threshold value, the
instrument will automatically enable the output
power limiter (see OLH parameter) and it
maintains this limit for a time programmed by tOL
parameter.
At instrument start up, if the tOL parameter is
equal to "InF", the P15 setting has no effect.
GB
GB
GB
GB
GB
11
Real
curve
Adjusted
curve
P13