DEFAULT CONFIGURATION
DEFAULT CONFIGURATION
DEFAULT CONFIGURATION
DEFAULT CONFIGURATION
DEFAULT CONFIGURATION
PARAMETERS
PARAMETERS
PARAMETERS
PARAMETERS
PARAMETERS
The configuration parameters can be loaded with
predetermined default values. These data are the
typical values loaded in the instrument prior to
shipment from factory. To load the default values
proceed as follows:
a ) The internal switch (V2, see fig. 13) should
be open.
b) The upper display will show:
C n F
C n F
C n F
C n F
C n F
c) Push the
pushbutton; the lower display will
show the firmware version.
C n F
C n F
C n F
C n F
C n F
A. 0 1
A. 0 1
A. 0 1
A. 0 1
A. 0 1
d) Maintaining the pressure on the
pushbutton
push the
pushbutton also.
The instrument will show
O F F
O F F
O F F
O F F
O F F
d F L
d F L
d F L
d F L
d F L
e ) Press
pushbutton to select between table 1
(european) or table 2 (american) default
parameter set. The display will show:
TMS-A-01.pmd
2
t b. 1
t b. 1
t b. 1
t b. 1
t b. 1
d F L
d F L
d F L
d F L
d F L
f) Press FUNC pushbutton; the display will show:
L. d t.
L. d t.
L. d t.
L. d t.
L. d t.
This means that the loading procedure has been
initiated. After about 3 seconds the loading
procedure is terminated and the instrument
reverts to visualization as in point b).
The following is a list of the default parameters
loaded during the above procedure:
PARAMETER
TABLE 1
TABLE 2
P1
1
9
P2
0 °C
0 °F
P3
400 °C
999 °F
P4
H
H
P5
rEL
rEL
P6
Air
Air
P7
1
1
P8
HA
HA
P9
OFF
OFF
P10
0
0
P11
HA
HA
P12
OFF
OFF
P13
0
0
P14
0
0
P15
0
0
P16
OFF
OFF
P17
10 A
10 A
P18
0
0
P19
rEv
rEv
A. 2
16/02/2005, 14.39