Family Aqua Condens 3.5 BIS
For the calculation a comfort temperature of 20° is assumed (the
value 20 is used exclusively for the choice of the curve and does not
limit the possibility to adjust the ambient temperature to higher levels)
and is calculated using the following formula:
design delivery temp. -20
P. 45 = 10 x
20- min. design external T.
If the calculation produces an intermediate value between two
curves, you are advised to choose the compensation curve nearest
the value obtained.
Example: if the value obtained from the calculation is 9, this is
between curve 7.5 and curve 10. Choose the nearest curve, i.e. 10.
Note: if the memory function is ON, the boiler turns on at the delivery
temperature calculated according to the value detected by the
external probe, and increases the memorised delivery temperature
by 5°C after 10 minutes.
Memory repeats the cycle until the ambient temperature set on
the ambient thermostat is reached, or until the maximum permitted
temperature is reached. In this case the lower thermoregulation curve
should be selected. Select curve 7.5 following the previous example.
THERMOREGULATION CURVES
Curve di Compensazione Climatica
100
90
80
70
60
50
40
30
20
20
15
10
5
OUTSIDE TEMPERATURE (°C)
Climatic curve correction
The heat request is made by the closure of the room thermostat
contact, while the opening of the contact produces a switch-off.
The delivery temperature is calculated automatically by the boiler,
nevertheless the user can change the delivery temperature by means
of the control panel, as done for the modification of the HEATING
SET-POINT.
Pressing the
key will display a value that can vary by turning the
encoder between +5 and -5.
The modification of this value will not directly modify the delivery
temperature, but will affect the calculation that determines the value
of that temperature, altering the comfort temperature in the system
(20).
We therefore have the possibility to choose between 11 levels of
comfort.
14
35
32,5
30
25
22,5
40
37,5
27,5
40
0
-5
-10
-15
Temperatura Esterna (°C)
90
80
70
60
50
40
30
20
10
30
25
20
- If the BAG2 MIX is used, accessory on request, 2 thermoregulation
curves can be used
- PARAMETER 46 = 1 ON
- OTC 1 CH PARAMETER 45 for the direct mode system
- OTC 2 CH PARAMETER 47 for the mixed mode system
To determine the curve for the mixed system acts as described for
the parameter 45.
20
To program the Max Heating Set Point, use PARAMETER 31.
17,5
To program the Min Heating Set Point, use PARAMETER 32.
For the correction of the curve in this configuration, refer to the
15
instructions supplied with the BAG2 MIX.
P. 21
12,5
Type of heat request PARAMETER 51
If the boiler is connected to a room thermostat or timed thermostat,
10
set PARAMETER 51 = 0.
7,5
When the environment cools below the value set on TA, the contact
closes and the boiler turns on according to the programmed settings.
5
When the environment returns to the desired temperature, the
contact opens and the boiler shuts down.
2,5
P. 22
If the boiler is connected to a programmable timer, set PARAMETER
51 = 1.
-20
With the contact closed, to set the time of the programmable timer,
the boiler turns on according to the programmed settings.
With the contact open, the thermoregulation of the boiler is placed on
NIGHT at 16° C and calculates the delivery temperature according to
the new conditions.
The delivery temperature can vary acting as described above.
If the BAG2 MIX is used, set PARAMETER 52 as described for 51.
PARALLEL NIGHT-TIME REDUCTION
90
80
70
DAY climatic curve
60
50
40
30
20
10
20
15
Memory function PARAMETER 43
The Memory function acts by increasing the delivery T° by 5° C if
after 10 minutes of closing of the TA the T° set on the TA has not yet
been reached, and continues to increase the delivery T° up until the
opening of the TA or until the MAX HEATING SET POINT is reached.
Therefore you should consider leaving the function on. Setting
PARAMETER 43 = 1 ON or cancelling it 43 = 0 OFF.
CLIMATIC CURVE CORRECTION
15
10
5
0
-5
OUTSIDE TEMPERATURE (°C)
Riduzione notturna P A RALLELA
Curva climatica GIORNO
Curva climatica NOTTE
NIGHT climatic curve
10
5
0
-5
OUTSIDE TEMPERATURE (°C)
Temperatura Esterna
-10
-15
-20
-10
-15
-20