Code
foncti
Nom
on
start voltage setting
B052
OV-LAD Stop level of
non stop operation
setting
B053
Deceleration time of
non stop operation
setting
B054
Frequency width of
quick deceleration
setting
B055
DC bus AVR P-gain
B056
DC bus AVR I-time
B080
[AM]analog signal
gain
B082
Start frequency
adjustment
B083
Carrier frequency
setting
B084
Initialization mode
(parameters or trip
history)
B085
Country for
initialization
Liste des registres de maintien
R/W
Description
start non stop operation. Range
is 0.0 to 1000.0
R/W Setting the OV-LAD stop level of
non stop operation. Range is 0.0
to 1000.0
R/W Range is 0.1 to 3000
R/W Setting of the first quick
deceleration width. Range is 0.0
to 10.0
R/W Proportional gain adjustment for
DC bus AVR function. Range is:
0.2 to 5.0
R/W Integration time adjustment for
DC bus AVR function. Range is:
0.0 to 150.0
R/W Adjust of analog output at
terminal [AM],
range is 0 to 255
R/W Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
R/W Sets the PWM carrier (internal
switching frequency), range is
2.0 to 12.0 kHz
R/W Select the type of initialization
to occur, three option codes:
00...Trip history clear
01...Parameter initialization
02... Trip history clear and
parameter initialization
R/W Select default parameter values
for country on initialization,
three option codes:
00...Japan
01...Europe
02...US
B-33
Données du réseau
Registre.
Plage
Résolution
10CBh 0 to 10000
10CCh 1 to 30000
0.1 sec
10CEh
0 to 100
0.1 Hz
1173h
2 to 50
1174h
0 to 1500
10CFh
0 to 255
10D1h
5 to 99
0.1 Hz
10D2h
20 to 120
0.1 Hz
10D3h
0, 1, 2
10D4h
.
0.1 V
0.1
0.1s