B-38
C102
Reset selection
C141
Input A select for logic
output
C142
Input B select for logic
output
C143
Logic function select
Determines response to Reset input
[RS].
Three option codes:
00...Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01...Cancel trip state at signal OFF
transition, stops inverter if in
Run Mode
02...Cancel trip state at input ON
transition, no effect if in Run Mode
R/W
See "Output Logic and Timing" on
page 3–63
R/W
R/W Applies a logic function to calculate
[LOG] output state, Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
114Ah
0, 1, 2
1150h
0, 1, 2, 3,
4, 5, 6, 7,
8, 10, 43
1151h
1152h
0, 1, 2