B-28
Code
foncti
on
A071
PID enable
A072
PID proportional gain
A073
PID integral time
constant
A074
PID derivative time
constant
A075
PV scale conversion
A076
PV source setting
A077
Reverse PID action
A078
PID output limit
A081
AVR function select
A082
AVR voltage select
A085
Operation mode
selection
A086
Energy saving mode
tuning
Liste des registres de maintien
Nom
R/W
R/W Enables PID function,
two option codes:
00 ...PID Disable
01 ...PID Enable
R/W Proportional gain has a range of
0.2 to 5.0
R/W Integral time constant has a
range of 0.0 to 150 seconds
R/W Derivative time constant has a
range of 0.0 to 100 seconds
R/W Process Variable (PV), scale
factor (multiplier), range of 0.01
to 99.99
R/W Selects source of Process
Variable (PV), option codes:
00 ...[OI] terminal (current in)
01 ...[O] terminal (voltage in)
02 ...ModBus network
10 ...Calculate function output
R/W Two option codes:
00 ...PID input = SP-PV
01 ...PID input = -(SP-PV)
R/W Sets the limit of PID output as
percent of full scale,
range is 0.0 to 100.0%
R/W Automatic (output) voltage
regulation, selects from three
type of AVR functions, three
option codes:
00 ...AVR enabled
01 ...AVR disabled
02 ...AVR enabled except during
deceleration
R/W 200V class inverter settings:
00...200
01...215
02...220
03...230
04...240
400V class inverter settings:
00...380
01...400
02...415
03...440
04...460
05...480
R/W Two option codes:
00...Normal operation
01...Energy-saver operation
R/W Range is 0.0 to 100 %
Description
Données du réseau
Registre.
Plage
Résolution
1068h
0, 1
1069h
2 to 50
106Ah
0 to 1500
0.1 sec
106Bh
0 to 1000
0.1 sec
106Ch
1 to 9999
106Dh
0, 1, 2, 3
106Eh
0, 1
106Fh
0 to 1000
0.1 %
1070h
0, 1, 2
1071h
0 to 5
1072h
0, 1
1073h
0 to 1000
0.1 %
.
0.1
0.01