Manuel utilisateur, Rev. 2.0, oct. 2019
COMMAND LIST
Description
Adjustable baud rate for
RS485
Gain adjustment for
temperature value
DHCP/BOOTP
Offset adjustment for
temperature value
Device special information
(remark)
Emissivity internal
Error code
Emissivity source selection:
Constant / Analog input /
Rotary switch
Valley hold time
Average time
Gateway Address
Temperature value
responding to the top of
current / voltage output
range
Device ambient
temperature
IP Address
104
1.800.561.8187
Char Value Format Poll
Burst Set Legal values
D
nnnn
DG
n.nnnn
DHCP n
DO
nnnn.n
DS
XXX
E
n.nnn
EC
nnnn
ES
X
F
nnn.n
G
nnn.n
GW
nnn.nnn.nnn.n
nn
H
nnnn.n
I
nnn.n
IP
nnn.nnn.nnn.n
nn
www.
Factory default 2-W 6-W 12-W 4-W
0048 = 4800 baud rate
0096
0096 = 9600 baud rate
0192 = 19200 baud rate
0384 = 38400 baud rate
0576 = 57600 baud rate
1152 = 115200 baud rate
0.8000 ~ 1.2000
1.0000
0 = OFF, 1 = DHCP ON
0
2 = BOOTP ON
-200.0 ~ 200.0°C / -360.0 ~
0000.0
360.0°F
In current unit (°C/°F)
e.g. FPI-RAYTEK
0.100 ~ 1.100
0.95
2W, 6W, 12W
0001 = Target temp. over
range
0002 = Target temp. under
range
0010 = Ambient temp. over
range
0020 = Ambient temp. under
range
0100 = Analog output over
range
0200 = Analog output under
range
4W:
00000004 = Ambient temp.
over range
00000008 = Ambient temp.
under range
00000200 = Target temp. over
range
00000400 = Target temp.
under range
00020000 = Profinet not ready
I = set by a constant number
I
according to the command "E";
S for 2-wire
E = set by the input voltage on
sensor
FTC1 (only for 12-wire);
S = set by the rotary switch
(only for 2-Wire)
000.0 ~ 998.9 secs;
000.0
999.0 = infinite
0 = no averaging;
000.0
0.1 ~ 999.0 secs
0.0.0.0 - 255.255.255.255
192.168.42.1
(Bottom temperature of current
Upper-limit of
/ voltage output range + 20°C)
temperature
~ Upper-limit of temperature
range
range.
In current unit (°C/°F)
In current unit (°C/°F)
EIHH over range
EIUU under range
0.0.0.1 - 255.255.255.255
192.168.42.134
information@itm.com