2 SPECIFICATION
2.5 TECHNICAL DATA
Environment
Ambient temperature
Relative humidity
Protection rating
Materials
Housing
Cover
Front foil
Screws
Cable glands
Cable clip
Electrical features
Power supply
Polarity reversal
Current consumption
Output current
Pulse output
Relay output
Electrical wiring
0 to 60 °C (use and storage)
max 80 %, non condensated
IP65 (wall-mounted and front side of panel-mounted version)
IP20 (rear side of panel-mounted version)
PC (panel-mounted) - ABS (wall-mounted)
PC
Polyester
Stainless steel
PA
PA
13-30 VDC (L+) ± 10%, filtered and regulated, or
115/230 VAC - 50/60 Hz (see technical specifications
115/230 VAC, below)
protected
(Without consumption of pulse output and sensor supply):
70 mA version with relays
20 mA version without relay
4...20 mA, sourcing or sinking mode connection
Loop impedance max:
1200 Ω at 30 VDC; 900 Ω at 24 VDC;
450 Ω at 15 VDC; 300 Ω at 13 VDC;
1000 Ω when supplied with 115/230 VAC
polarized, potential free, 5 - 30 VDC, 100 mA, protected.
Line drop at 100 mA: 1.5 VDC
2 relays, 3 A, 230 VAC ou 40 VDC, programmable
Through shielded cable, 1.5 mm
50 m max. length (P. supply, current and pulse outputs)
max. cross-section 1.5 mm
E-6-
8025 UNIVERSAL
2
max. cross-section,
2
(relay)