2.4
FLUE
The flue must be well isolated and circular if possi-
ble. The flue must not have defects, narrowings or
losses. All the inspection doors must be closed and
2.5

CHIMNEY POT

The chimney pot must have an exit section dou-
bled than the one of the chimney, in order to make
easier the exit of the smoke. The chimney pot must
be enough tall to lean out over the reflow zone
2.6
CONJUNCTION
The conjunction of the stove to the flue must be
as short as possible and must not have horizontal
or not much inclined parts. The counterslope parts
are forbidden and must be absolutely avoided.
Near the conjunction, inflammable materials must
not be present. The conjunction must not go inside
2.7
CORRECT CONJUNCTION TO THE CHIMNEY
If the conduct of the chimney starts from a lower
floor than the connection point of the stovr, it may
be necessary to close the conduct under the con-
nection pipe with fireproof materials.
The connection with the chimney must be always
well fixed and sealed, it must not have narrowing
NO
Picture 5 - Examples of correct and incorrect connection of the chimney
2.8

AIR INTAKE

The standard installation of the stove considers
that the comburent air is taken directly from the
room where the stove is installed. In this case,
in the room must be always ensured the recycle
of fresh air, in particular if the room is small and
window and door frames are hermetic. The cor-
well sealed. The connection of other devices to the
same chimney is not allowed.
generated by the roof: if you are not sure about
this contact experienced technicians. If you are
in a windy place, it might be necessary to install
windproof devices.
the flue. To increase the safety of the conjunction,
we suggest to install a washer on the wall being
sure that the connection between the washer and
the chimney is walled and well sealed. Also the
connection between the stove and the conjunc-
tion must be fixed and sealed.
and must not decrease the usable section of the
chimney (see picture 5). If near the stove there is
inflammable material or high temperatures sensi-
ble, the connection must be isolated and the safe-
ty distances must be strictly observed.
NO
NO
rect flow of air in the room must be ensured also
in presence of other combustion based devices,
aspiring hoods, chimneys and vent-holes. The air
intake in the room must have a minimum surface
of 80 cm2. On demand, Rizzoli can give specific
valves which can allow the automatic opening of
50