8.3.11 end
To quit the respective menu level, select the menu item END with the arrow
keys.
The settings made are saved on leaving the configuration menu.
SP
s
Hz
%
HI
PV
mA
V
LO
,
Illustration
8-15: End
8.4 Works Settings of the control electronics
Menu item
InP
Out / VALV
Out / VAdJ
Out / AdJ
deLY
Cut
PArA
Addr
SPOS
40 - 8605
factory setting comment
0 ... 10 V
input signal 0 ...10 V selected
- - - -
no valve selected
OFF
manual fine tuning of the valve fre-
quency inactive
LO: 2 mA
these values are changed by a valve
selection
HI: 200 mA
LO: 0.0 s
ramp function inactive
HI: 0.0 s
LO: 2.0 %
zero point cut-off active at 2 %
SEt2
controller parameter set 2 selected
0
Address 0 for the serial communica-
tion selected
0.0 %
Safety setting 0 % at an input signal
below 4 mA (with selection of the
4 ... 20 mA input signal) selected