8.3.6 cut (cut off) - Zero point cut-off
In order to guarantee leak-tight closing of the valve, the valve is completely
de-energised with input signals below the set limit (0.1 to 5.0 % of the set
standard signal) when the zero point shutdown is active.
In addition to its control function, the valve can also take on the function of a
cut-off valve.
Illustration 8-10: Cut (Cut off) - Zero point cut-off
nOTe!
With a set value of 0.0 %, the zero point cut-off is deactivated. Even
at an input signal of 0 %, the valve no longer reliably shuts off the flow.
The valve flow control restarts with a hysteresis of 0.5 %.
The reactivation of the current controle starts as soon as the input
signal is set to a value 0.5 % above the defined threshold value; i. e.
there is a hysteresis of 0.5 % for the activation and deactivation of the
cut off function.
The range of the input signal lying below the set threshold is no longer
available for the current control and fluidic flow control.