Télécharger Imprimer la page

Briggs & Stratton 076350 Manuel D'installation page 48

Publicité

48kW & 62kW
Rated Power Factor 0.8
Rated AC Voltage
Phase
Rated Frequency
Normal Operating Range
Output Sound Level
Shipping Weight
* Natural gas rating will depend on specific fuel but typical derates are between
10 to 20% off the LP gas rating.
** Determine Voltage and Rated Amps using the chart to the right.
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association)
standard C22.2 No. 100-4 (motors and generators).
48
Generator Specifications
(at 40°C/104°F, LP or NG):
See chart**
See chart**
Three phase
60 Hertz
-20°F (-28.8°C) to 104°F
(40°C)
65 dB(A) at 23 ft. (7 m)
at normal load
2355 lb (1068 kg)
Series 48000*
Voltage
3 Phase Wye
120/208
139/240
3 Phase Wye
3 Phase Delta
120/240
240/416
3 Phase Wye
3 Phase Wye
277/480
346/600
3 Phase Wye
Series 60000*
Voltage
120/208
3 Phase Wye
3 Phase Wye
139/240
3 Phase Delta
120/240
3 Phase Wye
240/416
3 Phase Wye
277/480
346/600
3 Phase Wye
Rated Amps
167
144
144
83
72
58
Rated Amps
215
186
186
108
93
75
BRIGGSandSTRATTON.COM