Frame
Size
1, 2
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 15 Amperes and respectively 240 or 480 Volts min.".
3
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240 (1-phase) or 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in
accordance with UL 489, rated 30 Amperes and respectively 240 or 480 Volts min.".
4
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 480 (3-phase) V max, when Protected by Circuit Breaker (inverse time trip type) in accordance with UL
489, rated max. 125 Amperes and 480 Volts min.".
1
"Suitable for motor group installation on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, DC 715 V max, when Protected by 50 215 26 from SIBA rated max. 20 Amperes"
1)
7.3 "Caractéristiques électriques "
UL / CSA pour des appareils avec une puissance nominale de 30 kW à 90 kW :
Pour des appareils ayant une puissance nominale de 30 kW / 40 hp à 90 kW / 125 hp, la certification
selon UL / CSA est en préparation.
UL / CSA pour des appareils à partir d'une puissance nominale de 110 kW :
Les appareils avec une puissance nominale de 110 kW / 150 hp ou 132 kW / 180 hp ou bien 163 kW /
220 hp ne sont pas certifiés selon UL / CSA.
BU 0600 fr-2324