Fig. 7: Set parameter
Menu no.
Parameter/
info
1.00
Setpoints
1.04
Main pump
switch-on
pressure
1.05
Main pump
switch-off
pressure
1.06
Main pump
stop delay
1.18
Rainwater
storage tank
pump start-
ing time
1.19
Rainwater
storage tank
pump stop-
ping time
1.25
Delta p in
TWM
1.26
Duration
time pres-
sure com-
pare
42
In the event of an error (active alarm), the touchscreen lights up red. After the problem has
been solved, the touchscreen must be "reset" to return to normal operation. The values are
set using the arrow keys.
Example of setpoint menu
a
Select the parameter to be set – switch to another menu level
b
b
Navigation row
c
c
Scroll navigation up / down
Menus and sub-menus
MP: HiMulti3 main pump
CP: Rainwater storage tank pump
TWM: Drinking water mode
RWM: Rain water mode
Min.
Max.
Text
1.0
4.9
1.0
4.9
1.0
120
-60
+60
-60
+60
-0.7
+0.7
0
300
NOTICE
There are 3 access levels for the settings. The access level can be
changed from level 1 to level 2 in menu 7.01. If not operated after 6
minutes have elapsed, it is automatically reset to level 1. Level 3 is re-
served for Wilo customer service.
Standard
Unit
Ac-
cess
level
1
1.2
bar
1
3.5 (HiM-
bar
1
ulti3-24);
4.4 (HiM-
ulti3-25);
4.9 (HiM-
ulti3-45)
20
s
2
2
s
2
-2
s
2
+0.2
bar
2
30
s
2
Installation and operating instructions • Wilo-RAIN3 • Ed.05/2024-02
Description
Sub-menu with values for setting the set-
point
Nominal pressure for switching on the
main pump (MP)
Nominal pressure for switching off the
main pump (MP) depends on the charac-
teristic curve selected in menu 5.04; set-
point must be at least 0.5 bar above the
start-up pressure
Delay in switching off a pump when the
switch-off value is reached and the cur-
rent value is still above this
Starting time relative to the start-up of
the main pump (MP)
Switch-off time relative to the start-up of
the main pump (MP)
Switch-off pressure difference between
TWM (drinking water mode) and RWM
(rainwater mode)
To protect the pump during operation and
when the pump no longer reaches the
switch-off pressure, a time can be set in
menu 1.26 after which the switch-off
pressure is reduced.
Defines the time after which the switch-
off pressure is reduced by the value set in
menu 1.27.