10.0 adjustments
adjustments
EN
10.1
venturi adjustment
WARNING
!
Carbon can be distributed in surrounding living area if the air shutter is improperly adjusted.
This appliance has an air shutter that has been factory set open according to
the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will cause
a more blue flame, but can cause flame lifting from the burner ports. The flame
may not appear yellow immediately; allow 15 to 30 minutes for the final flame
colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER.
note:
It is important that the orifice is securely inserted into the venturi.
10.2
flame characteristics
It's important to periodically perform a visual check of
the pilot and burner flames. Compare them to the
illustration provided. If any flames appear abnormal,
call a service person.
Birch Log Set BLKRS36
Oak Log Set OLKRS36
32
W415-10001315 / D-0 / 07.10.24
DEXEN EI
VENTURI ADJUSTMENT CHART
Flame must envelop
NG
1/16" (1.6mm)
LP
1/4" (6.4mm)
(12.7mm - 9.5mm) of
DEXEN EI
ODS - MILLIVOLT
PSE THERMOCOUPLE
(9.5mm - 12.7mm)
Flame must envelop
3/8" to 1/2"
(12.7mm - 9.5mm) of
thermocouple
SIT ELECTRONIC IGNITION
(9.5mm - 12.7mm)
Flame must envelop
(12.7mm - 9.5mm) of
SIT MILLIVOLT
(9.5mm - 12.7mm)
VENTURI
BURNER
33.2
ORIFICE
VENTURI
2-WAY PILOT
BURNER
3/8" - 1/2"
(9.5mm - 12.7mm)
33.1
upper
3/8" to 1/2"
Flame sensor
ADD IMAGE
HERE
36.1
3/8" - 1/2"
Birch Log Set BLKRS42
upper
3/8" - 1/2"
upper
3/8" to 1/2"
Flame sensor
Oak Log Set OLKRS42
3/8" - 1/2"
AIR
SHUTTER
OPENING
AIR
SHUTTER
OPENING
ORIFICE
3/8" - 1/2"
(9.5mm - 12.7mm)
La flamme doit envelopper
la sonde de flamme de
3/8" à 1/2"
(9.5mm - 12.7mm)
3/8" - 1/2"
(9.5mm - 12.7mm)
La flamme doit envelopper
la thermocouple de 3/8" à
1/2"
(9.5mm - 12.7mm)
3/8" - 1/2"
(9.5mm - 12.7mm)
La flamme doit envelopper
la sonde de flamme de
3/8" à 1/2"
(9.5mm - 12.7mm)
3/8" - 1/2"
(9.5mm - 12.7mm)