WARNING
!
Risk of fire. Maintain specified air space clearances to vent pipe and appliance.
The vent system must be supported every 3' (0.9m) for vertical runs. Use support ring assembly W010-0067 or
equivalent non-combustible strapping to maintain the minimum clearance to combustibles.
All vent measurements start at the base of the air collar of the appliance.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is
required.
note:
The appliance has a Heat Exhaust Management Kit (RSOHEM) which must use approved B-vent components.
24" (610mm) min. (above anything within
a 10 ft [3m] radius horizontally)
note:
A 36" (914mm) minimum vertical rise
is considered the minimum practical
dimension for the specific appliance
enclosure and a minimal building structure.
4.0 venting requirements (optional)
venting requirements (optional)
base of air
36" (914mm)
minimum
40 ft (12m)
maximum
36" (914mm)
minimum
collar
W415-10001315 / D-0 / 07.10.24
EN