C. For power cord installations only (see the next step if using conduit), assem
ble the strain relief in the hole. Insert the power cord through the strain relief
and tighten. Allow enough slack to easily attach the cord terminals to the
terminal block. If tabs are present at the end of the winged strain relief, they
can be removed for better fit.
NOTICE
Do not install the power cord without a strain relief. The strain relief bracket
MUST be installed before reinstalling the terminal block cover. You must
purchase a cord at the desired length that matches the receptacle
configuration correctly.
NOTICE
Next to this knockout ring [1-3/8" (3.5 cm) ], a knockout ring [1-1/8" (2.9 cm])
is reserved for installation to match some models of power cord and conduit.
D. For 3/4" conduit installations only, pur chase a squeeze connector matching
the diameter of your conduit and as semble it in the hole. Insert the conduit
through the squeeze connector and tighten. Allow enough slack to easily
attach the wires to the terminal block.
NOTICE
Do not install the conduit without a Squeeze connector.
Terminal
Block Cover
Screw to remove
Terminal Block Cover