2.1.10 Model with a terminal box

DANGER!
Risk of explosion!
Only permanently laid cables and wiring may be inserted.
The operator must provide suitable stress relief.
Wires with an outside diameter of 6 to 13 mm may be used. Observe
the maximum thermal loading of the cables or wires to be inserted.
The inserted break-off seal must be matched to the diameter of the
cable or wire.
The rated cross-section of the cable or wire strands must be at least
0.75 mm² and may not exceed 2.5 mm².
The screws for fixing the cover of the terminal box must be tightened
with a torque of 100 Ncm (±5%).
The solenoid coils may also be executed with a terminal box, with or without
fuse/contactor (to separate Design Type Inspection Certificate) as desired.
For protection against inadvertent opening of the cover, the latter bears the
marking:
Open only when the voltage is switched off!
14 - 03 ATEX 1030 X