TYPICAL 20 LB PROPANE GAS SUPPLY INSTALLATION
The remote tank enclosure kit provided with your Weber Built-In Grill shall be used for
installations using a 20 lb LP cylinder, mounted in an "island" structure.
The remote tank enclosure shall house the included hose and regulator assembly and
gas connections, the tank bracket and the fuel scale for connecting a remote mounted
LP cylinder to the Summit
Built-In Gas Grill. The hose and regulator are listed as
®
required parts of the CSA-listed Summit
A properly installed tank enclosure meets the requirements for venting, tank retention,
and separation of the LP cylinder from a heat source as outlined in the ANSI Standard
for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.
You need to hire a licensed contractor or licensed plumber and they need to follow the
requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances,
Z21.58/CSA 1.6 for LP enclosures.
The requirements described in the Standard for Outdoor Cooking Gas Appliances,
Z21.58/CSA 1.6. are as follows:
A remote enclosure for an LP gas cylinder shall be ventilated by openings at both
the upper and lower levels of the cylinder. This shall be accomplished by one of the
following:
A) One side of the remote LP cylinder enclosure shall be completely open; or
B) If the remote LP cylinder enclosure is designed to have four sides, a top, and a
bottom, ventilation is required for the remote LP cylinder enclosure;
a)
There should be at least two ventilation openings (a hole or group of holes
for the purpose of ventilation) in the sidewalls of the "island" structure. The
openings should be located within five inches (127 mm) of the top of the
enclosure. The ventilation openings should be equally sized and spaced at a
minimum of 90 degrees, and be unobstructed. The openings shall have a total
free open area of not less than 20 square inches. (This relates to one square
inch of ventilation area per pound of stored fuel capacity.)
b)
Ventilation openings (a hole or group of holes for the purpose of ventilation)
should be provided at floor level. The ventilation openings should have a total
free area of not less than 10 square inches. (This relates to
ventilation area per pound of stored fuel capacity.) There should be at least two
ventilation openings if the ventilation openings at floor level are in the sidewall.
The ventilation openings should be within five inches (127 mm) of the floor. The
ventilation openings should be of equal size and be spaced at a minimum of 90
degrees, and should be unobstructed.
c)
The minimum size of the ventilation hole(s) should not be less than
d)
The ventilation openings in the sidewalls should not allow venting into the
empty or "hollow" area of the "island." If a gas leak should occur or the LP
cylinder should vent in the LP cylinder enclosure, the gas should not be allowed
to vent or migrate into the empty or "hollow" area of the "island." Ventilation
openings in the sidewalls of the enclosure should only communicate with the
outside of the "island" structure, so that the gas can dissipate outside of the
"island" structure.
C) If the remote LP cylinder enclosure has four sides, a top and a bottom, and is
intended for installation in a built-in "island" enclosure;
a)
At least one ventilation opening (a hole or group of holes for the purpose of
ventilation) needs to be on one side of the enclosure that communicates with
the outside of the "island" structure. If a gas leak should occur or the LP
cylinder should vent in the LP cylinder enclosure, the gas should not be allowed
to vent or migrate into the empty or "hollow" area of the "island." Ventilation
openings should only communicate with the outside of the "island" structure,
so that the gas can dissipate outside of the "island" structure. The ventilation
opening should be located within five inches (127 mm) of the top of the
enclosure, and should have a total free area of 20 square inches. (This relates
to one square inch of ventilation area, per pound of stored fuel.)
b)
At least one ventilation opening (a hole or group of holes for the purpose of
ventilation) needs to be on one side of the enclosure that communicates with
the outside of the "island" structure, at the bottom. If a gas leak should occur
or the LP cylinder should vent in the LP cylinder enclosure, the gas should not
be allowed to vent or migrate into the empty or "hollow" area of the "island."
Ventilation openings should only communicate with the outside of the "island"
structure, so that the gas can dissipate outside of the "island" structure. The
ventilation opening should be located within five inches (127 mm) of the bottom
of the enclosure, and should have a total free area of 10 square inches. (This
relates to
square inch of ventilation area, per pound of stored fuel.)
1
4
c)
The minimum size of the ventilation hole(s) should not be less than
mm).
D) The remote LP cylinder enclosure should be constructed with non-combustible
materials. The remote LP cylinder enclosure should isolate the LP cylinder from the
burner compartment, so that it provides shielding from radiation, be a flame barrier
and provide protection from foreign material such as hot drippings.
E) There should be a minimum of two inches (50.8 mm) between the ground and the
floor of the remote LP cylinder enclosure.
F)
The LP cylinder valve should be readily accessible for hand operation. A door on the
remote LP cylinder enclosure to gain access to the LP cylinder valve is acceptable,
provided it is non-locking and can be opened without the use of tools.
28
Built-In Gas Grill.
®
square inch of
1
2
GAS SUPPLY
Use of any hose and regulator assembly other than that
provided or recommended by Weber-Stephen Products LLC
could be dangerous, and may not provide adequate gas supply
to the Summit
®
explosion causing serious bodily injury or death, and damage to
property.
Failure to build a remote LP cylinder enclosure for a single 20
lb cylinder only, following the requirements for ventilation,
cylinder retention and separation of the LP cylinder from a heat
source, listed in the ANSI Standard for Outdoor Cooking Gas
Appliances, ANSI Z21.58 CSA 1.6, could be dangerous, and could
result in a fire or an explosion causing serious bodily injury or
death and damage to property.
If you do not follow the DANGER statements exactly, the Warranty on the Summit
Gas Grill will be voided.