the rotary actuator can be connected and operated in two dif-
ferent modes:
1.
Three points mode
2.
Open / Closed mode
N
-
1
Fig. 19: Three points mode
N
-
1
Fig. 20: Open/Close mode / Emergency current model in the oper-
ating instructions
If voltage is applied simultaneously to terminals 2 and 3,
terminal 2 is the leading one and the actuator moves to the
OPEN position.
procedure:
→
Loosen left cable gland 15 (see Figs.1 and 2) and feed through
the cable to be connected.
All manuals and user guides at all-guides.com
Type 3005
Installation
Ph
+
T/E
2
3
Ph
+
T/E
2
3
→
Connect cable according to the required control type to the terminal
strip Pos. B of the power supply card.
operating principle for open / Closed mode:
•
Switch open = actuator closes
•
Switch closed = actuator opens
Connecting feedback
The limit switches for the feedback are suitable for a
maximum voltage of 250V AC/DC - 5A.
The rotary actuator features two additional limit switch contacts which
are supplied by the factory in an open position. These can be used for
the feedback of the rotary actuator.
Power supply and control
T/E
1
2
3
Fig. 21: Internal wiring of drive
english
Feedback
4-6
5
7
FC2
FC1
D
FCF
C
C
D
B
A
FC0
Motor
=
25