3.3 Installation example: KESSEL Coalescence separator
Illustration shows KESSEL-coalescence separator system A with cover class B and sampling chamber.
3.4 Dimensioned drawing
OKB
L
L max.
NS
DN
Sludge trap
NS 3
150
1000 l
NS 6
200
2)
2500 l
NS 6
200
2)
5000 l
NS 10
150
1500 l
NS 10
200
2)
2500 l
NS 10
200
2)
5000 l
NS 15
200
5000 l
1) Comparable total sludge trap volume according to dimensioning of DIN EN 858
2) Eccentric reduction of inlet/outlet to DN 150 possible on site, fitted through DN 150 sample removal shaft
2020/09
T
L
B
min
2390
1200
840
1)
2590
1760
850
3110
1760
870
2910
1200
840
1)
2590
1760
850
3110
1760
870
3110
1760
870
Installation
B
Oil storage
max
h2
h1
215 l
1240
1100
1070
380 l
1230
1630
1600
470 l
1250
1630
1600
267 l
1240
1100
1070
380 l
1230
1630
1600
470 l
1250
1630
1600
470 l
1250
1630
1600
27/120
DN 150: T-T
DN 200: T-T
T-T
= Height above ground
EÜ
Class D: 700 mm ≤ T
Class A/B: 700 mm ≤ T
Overhang
Weight
L
max
395 kg
90 mm
2642
535 kg
120 mm
2940
610 kg
130 mm
3460
440 kg
100 mm
3162
535 kg
120 mm
2940
610 kg
130 mm
3460
610 kg
130 mm
3460
= 155 mm
EÜ
= 180 mm
EÜ
≤ 1.500 mm
EÜ
≤ 1.800 mm
EÜ
Total
mm
volume
1800
4300
5800
2600
4300
5800
5800
010-222