Télécharger Imprimer la page

Kessel Aqualift XL Serie Instructions De Pose Et D'utilisation page 31

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 38
Information / pump type
Weight
Power P1 / P2
Speed
Operating voltage
Rated current
Max. pumping capacity
Max. pumping height
Max. temperature
Pumped medium
Protection rating
Protection class
Motor protection
Connection type
Connecting cable (5 m)
Type of fuse required (Mono)
Type of fuse required (Duo)
Operating mode
Enter the system parameters at the control unit
After initialising the control unit, enter the following system parameters.
Comfort 230V control unit
Type Aqualift: lifting station XL xxx l (xxx = tank volume)
Pump type: as stated on delivery note
Comfort 400V control unit
Select the suitable system in Menu 3.6 Performance variable.
If this is not available for selection, select special system as follows:
Pump type
SPF 1500
SPF 3000
SPF 4500 or SPF 5500
Then set the parameters as shown in the following table or check the settings.
010-907
1400
1500
25 kg
24 kg
1.6 kW / 1.1 kW
1.4 kW / 1.1 kW
1370 rpm
1415 rpm
230 V; 50 Hz
7.3 A
2.7 A
38 m³/h
40 m³/h
7 m
8 m
integrated
coded
3 x 1.5 mm²
C10A
C20A
C16A
Adjustment in menu 3.6 Capacity
Special pump < 4 A
Special pump < 6.3 A
Special pump < 10.0 A
Lifting station/Installation and operating instructions
3000
24 kg
3.2 kW / 2.7 kW
4.5 kW / 3.7 kW
2845 rpm
2850 rpm
400 V; 50 Hz
5.4 A
47 m³/h
16 m
40 °C
IP68 (3 mWC/48 h)
I
external
Direct connection
7 x 1.5 mm²
C16A
C20A
S1 / S3
4500
5500
26 kg
32 kg
5.6kW / 4.8 kW
2840 rpm
7.5 A
9.1 A
55 m³/h
60 m³/h
20 m
27 m
6 x 1.5 mm
C20A
C20A
C32A
C32A
S3
31 / 114
2

Publicité

loading

Ce manuel est également adapté pour:

Aqualift xl 200Aqualift xl 300Aqualift xl 450