Electrical Connection / Earthing; Terminal Strip Positionning For Star (Y) And Delta () Connection (Multi-Voltages Electric Motors); Lower Voltage :  Connection; Higher Voltage : Y Connection - salmson NOLH Installation Et Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

 
 
Bracket sizes 55 and 65 : 
Connections : 
 Vp : pump drain connection : 
32‐125 to 50‐315 : G1/4'' 
65‐125 to 200‐250 : G3/8'' 
150‐500 to 300‐500 : G1/2'' 
 Vh : drain connection (if oil lubricated ballbearings) : G1/4'' 
 H : constant level oiler (if oil lubricated ballbearings) : G1/4'' 
 Rh : oil filling (if oil lubricated ballbearings) : 
Bracket sizes 25,35 and 45 : 15,7 
Bracket sizes 55 and 65 : 20 
 Eq : quench inlet : 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45 : G1/4'' 
 Er : mechanical seal heating inlet 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45 : G1/4'' 
 Bpe : stuffing box quench inlet : 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45, 55 and 65 : G1/4'' 
 Fe : external flushing : 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45 : G1/4'' 
 Sq : quench outlet : 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45 : G1/4'' 
 Sr : mechanical seal heating outlet : 
Bracket sizes 25 and 35 : G1/8'' 
Bracket size 45 : G1/4'' 
 Nh : oil level control for brackets 55 and 65 : G3/4'' 
All manuals and user guides at all-guides.com
Impeller  dia 
125
 
 
 
13 
 
7.3 ELECTRICAL CONNECTION / EARTHING 
Check  that  motor  winding  corresponds  to  site  electric  power 
supply characteristics before electrical connections are performed. 
Connecting  a  230/400V  motor  on  a  400V  power  supply  or 
connection  of  a  400/690V  motor  on  a  690V  power  supply  might 
drive  to  motor  destruction  if  terminal  strip  are  positioned  in  a  wrong 
way. 
 
Electrical connection should be performed by qualified personnel 
only  having  necessary  agreements  and  in  compliance  with  local, 
national and international regulations. 
 
Equipments used in an ATEX zone will be connected in compliance 
with CEI60079‐14. It is the responsibility of the end user to select 
proper type and size of electric cable. 
 
Respect  motor  manufacturer  instructions  to  make  electric  motor 
connection (refer to the instructions supplied with the motor. they 
are  usually  indicated  inside  motor  junction  box).  Sensors  will  be 
connected  in  compliance  with  the  instructions  given  in  dedicated 
instruction manual. 
 
7.3.1
TERMINAL  STRIP  POSITIONNING  FOR  STAR  
(Y)  AND  DELTA  () CONNECTION  (MULTI‐
VOLTAGES ELECTRIC MOTORS) 
Multi‐voltage winding for voltages  230/400V and 400/690V :  
 
6 wiring terminals : 
To  change  motor  direction  of  rotation  reverse  two  phases  on  wiring 
terminals. Connection of earthing terminal is mandatory. 
 
7.3.2
LOWER VOLTAGE :  CONNECTION 
Voltage : U 
 
 
7.3.3
HIGHER VOLTAGE : Y CONNECTION 
Voltage : U3 
 
  ENGLISH  
 
 