1 - Tank (heated for heavy oil)
2 - Filter (with resistance for oil > 7°E / 50°C)
3 - Forwarding pump
4 - Control manometer
5 - Shutter valves (in couple) excluding the burner
6 - Burner (provided for Kit for heavy oil code no. 3000721)
7 - Pressure adjuster (set as indicated in table below)
8 - Filter (with resistance for oil > 7°E / 50°C)
9 - Burner pump
10 - Gas separator
Change for supply in derivation
The gas separator for heavy oil shall be provided with an electric heater code no. 3010050.
Temperature fuel
°C
up to 80
90
100
110
120
NOTICES
- The oil could easily flow through the pipes if those are properly seized, protected and heated (by electricity, steam
or hot water).
- In order to limit gas or steam production the oil pressure into the gas separator (10) shall be set in function of the
supply temperature, see table above.
- The forwarding pump should have at least a double capacity than that one of the burner. For several burners sup-
plied through the same ring supply line, the forwarding pump should have a capacity of approx. 30% more than the
sum of the single burners outputs.
- For starting-up: after excluding the burner by the shutter valves (5) let the oil flow into the supply ring up to reach
the required circulation; after than open the valves and supply normally the burner.
5507
HEAVY OIL SUPPLY LINE
Pressure
bar
1
1,5
2
2,5
3
D1996
supply line
4
GB
to the burner