The table below give indication about self diagnostic routine. Some of error code requires activities
exclusively for Authorized Service Center.
Outdoor Unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER
PCB.
Display
101
Hydro Unit / Outdoor Unit communication connection error
122
EVA Inlet temp sensor SHORT or OPEN
123
EVA Outlet temp sensor SHORT or OPEN
162
EEPROM Error
198
Error of Terminal Block's Thermal Fuse(Open)
201
Hydro Unit / Outdoor Unit communication error(Matching error)
202
Hydro Unit / Outdoor Unit communication error(3 min)
203
Communication error between INVERTER and MAIN MICOM (4 min)
221
Outdoor Unit air temperature sensor error
231
Condenser temperature sensor error
251
Discharge temperature sensor error
320
OLP sensor error
403
Detection of freezing (During cooling operation)
Protection of Outdoor Unit when it is overload (during Safety Start,
404
Normal operation state)
407
Comp down due to high pressure
416
Discharge of a compressor is overheated
419
OUTDOOR UNIT EEV operation error
425
Power source line missing error (only for 3-phase model)
440
Heating operation blocked (outdoor temperature over 35 °C)
441
Cooling operation blocked (outdoor temperature under 9 °C)
458
OUTDOOR UNIT fan1 error
461
[Inverter] Compressor startup error
462
[Inverter] Total current error/PFC over current error
463
OLP is overheated
464
[Inverter] IPM over current error
465
Compressor overload error
466
DC LINK over/low voltage error
467
[Inverter] Compressor rotation error
468
[Inverter] Current sensor error
46
English
Explanation
Error Source
Hydro Unit
Hydro Unit
Hydro Unit
Hydro Unit
Hydro Unit
Hydro Unit/
Ourdoor Unit
Hydro Unit/
Ourdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit
Outdoor Unit