Locating the Units

Deciding on Where to Install the Outdoor
Unit
Decide the installation location regarding the following
condition and obtain the user's approval.
• The outdoor unit must not be placed on its side or
upside down, as the compressor lubrication oil will run
into the cooling circuit and seriously damage the unit.
• Choose a location that is dry and sunny, but not
exposed to direct sunlight or strong winds.
• Do not block any passageways or thoroughfares.
• Choose a location where the noise of the Air to water
heat pump when running and the discharged air do
not disturb any neighbours.
• Choose a position that enables the pipes and cables to
be easily connected to the indoor unit.
• Install the outdoor unit on a flat, stable surface that
can support its weight and does not generate any
unnecessary noise and vibration.
• Position the outdoor unit so that the air flow is directed
towards the open area.
• Place the outdoor unit where there are no plants
and animals because they may cause malfunction of
outdoor unit.
• Maintain sufficient clearance around the outdoor unit,
especially from a radio, computer, stereo system, etc.
• When installing the outdoor unit near seashore, make
sure it is not directly exposed to sea breeze.
If you can not find a adequate place without direct see
breeze, make sure to apply anti-corrosion coating on
the heat exchanger.
– Install the outdoor unit in a place (such as near
buildings etc.) where it can be prevented from sea
breeze which can damage the outdoor unit.
Outdoor
unit
Sea breeze
Sea
Outdoor
unit
Sea breeze
Sea
• If you cannot avoid installing the outdoor unit by the
seashore, construct a protection wall around to block
the sea breeze.
– Protection wall should be constructed with a solid
material such as concrete to block the sea breeze
and the height and the width of the wall should be
1.5 times larger than the size of the outdoor unit.
Also, secure over 700mm between the protection
wall and the outdoor unit for exhausted air to
ventilate.
Protection wall
Sea breeze
Sea
– Install the outdoor unit in a place where water can
drain smoothly.
• If you cannot find a place satisfying above conditions,
please contact manufacturer. Make sure to clean
the sea water and the dust on the outdoor unit heat
exchanger.
• Do not install the Air to Water Heat pump in following
places.
– The place where there is mineral oil or arsenic acid.
There is a chance that parts may get damaged due
to burned resin.
The capacity of the heat exchanger may reduce or
the Air to Water Heat pump may be out of order.
– The place where corrosive gas such as sulfurous
acid gas generates from the vent pipe or air outlet
The copper pipe or connection pipe may corrode
and refrigerant may leak.
– The place where there is a danger of existing
combustible gas, carbon fiber or flammable dust.
The place where thinner or gasoline is handled.
Outdoor
unit
9