Samsung AE044MXTPEH Mode D'emploi page 17

Masquer les pouces Voir aussi pour AE044MXTPEH:
Table des Matières

Publicité

AE120/160MXTP∗H
Using only Y-joint
Outdoor unit
Item
Longest piping length Less than 70m
Maximum
Outdoor unit
allowable
Equivalent length Less than 85m
~ Indoor units
length of pipe
Outdoor unit
Maximum
~ Indoor units
allowable
Indoor unit ~
height
Indoor unit
between indoor units
Maximum
First Y-joint
allowable
~ Last indoor
length of pipe
unit
Additional refrigerant
calculation
• Contact the manufacturer if the length should exceed.
EEV Kit
EEV Kit ~
Actual pipe lengh
Indoor units
• Please refer to the EEV Kit manual.
Total length
Less than 200m
Less than 30m
Height difference
Less than
15m
Actual piping
Less than 40m
length
R=Basic Charge + Additional charge by the piping length + Additional charge by (A2A)Indoor
Basic Charge : Up to 10m When Installing A2W only = 3500g
Additional charge by the piping length : 3/8" - 50g/m, 1/4" - 20g/m
Additional charge by (A2A)Indoor : Refer to the 16 page ' A mount of additional refrigerant for each indoor unit' table.
2m or less
MXD-E24K200A
MXD-E32K200A
20m or less
MXD-E24K232A
MXD-E24K300A
MXD-E32K224A
MXD-E32K300A
Using EEV kit
Outdoor unit
Example
a+b+c+d+e ≤ 70m
Y-joint and EEV kit : 0.5m
a+b+c+d+e+f+g+h+i ≤ 200m
H1
H2
b+c+d+e ≤ 40m (between first Y-joint and indoor unit)
h≤20m(between EEV kit and indoor unit)
Model name
MEV-E24SA
1 indoor
MEV-E32SA
MXD-E24K132A
2 indoor
3 indoor
EEV
kit
Remarks
10m ≤ Total length ≤ 200m
If outdoor unit is located
lower position H1 ≤ 25m
Remarks
Apply to products without EEV
(Wall mounted & ceiling)
English
17

Publicité

Table des Matières
loading

Table des Matières