Electrical Connections
Specification of Electronic Wire of the Outdoor Unit
Outdoor unit
AE044MXTPEH
AE066MXTPEH
AE090MXTPEH
AE120MXTPEH
AE160MXTPEH
AE090MXTPGH
AE120MXTPGH
AE160MXTPGH
NOTE
• The power cable is not supplied with the Air to water heat pump.
NOTE
• Select the thickness and length of power cable less than 10% of voltage drop from input voltage.
CAUTION
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• To protect the product from water and possible shock, you should keep the power cable and the connection
cord of the indoor and outdoor units in the iron pipe.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power cable and communication cable.
• Each indoor unit should be supplied between maximum and minimum voltage values (264V~198V).
• Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245 IEC 57 / CENELEC:H05RN-F , IEC:60245 IEC 66 /
CENELEC: H07RN-F)
32
English
Power Supply
Voltage Range
Hz
Volts
Min
198
198
50
220-240
198
198
198
342
50
380-415
342
342
MCA
Max
Min. Circuit Amps.
264
18.0
264
20.0
264
22.0
264
28.0
264
32.0
457
10.0
457
10.0
457
12.0
MFA
Max. Circuit Amps.
25.0
25.0
27.5
35.0
40.0
16.1
16.1
16.1