Vacuum Drying
• Use a manifold gauge for R410A to prevent the inflow of foreign substances and resist against the internal pressure.
• Use the vacuum pump with the check valve to prevent pump oil from flowing backward while the vacuum pump is stopped.
• Vacuum system to 5Torr (666.6Pa, 0.0067 kgf/cm², 5 mmHg).
• Close the service valve of the liquid side pipe and gas side pipe completely.