Adding Refrigerant
• The R410A refrigerant is blended refrigerant. Add only liquid refrigerant.
• Measure the quantity of the refrigerant depending on the length of the liquid side pipe. Add fixed quantity of the
refrigerant using a scale.
Adding refrigerants in cooling conditions
Manifold gauge
Low pressure
side
Scale
Adding refrigerants in heating conditions
Manifold gauge
Low pressure
side
Scale
• Connect the manifold gauge and purge the manifold gauge.
• Open the manifold gauge valve of the liquid side service valve and add the liquid refrigerant.
• If you cannot fully recharge the additional refrigerant while the outdoor unit is stopped, use the key on the outdoor
unit PCB to recharge the remaining refrigerant. (Refer to page 37.)