PRE-INSTALLATION CHECKLIST

A structural engineer approved the mounting structure.
I am familiar with the function of the safety cable.
The fan will be installed so that the airfoils are at least 10 ft (3.05 m) above the floor.
The fan will be installed so that the airfoils have a minimum of 2 ft (0.61 m) of clearance from
obstructions and the building structure.
The distance of the fan from the ceiling should be measured from the top of the airfoil tips to the
ceiling.
The fan will be installed so that it is not subjected to high winds such as from an HVAC system
or near a large garage door.
If the fan is mounted at the same level or higher than a diffuser, the airfoil tips must be at a distance
that is at least 1x the measure of the fan's diameter. If the fan is mounted at the same height or
below a diffuser, the airfoil tips must be at a distance that is at least 2x the measure of the fan's
diameter.
The distance between multiple fans will be at least 2.5x the fans' diameter when measured
from the centers of the fans.
The airfoils and other fan components are those that were shipped with the motor unit.
If installing multiple fans, do not mix and match fan components.