Wiring: Fire Signal Relay

WARNING: Improper installation can cause electric shock or damage to the motor and controller. A
qualified electrician should perform the installation.
If installing the fan in the United States, the fan must be installed per the following National Fire Protection
Association (NFPA) guidelines:
• The fan must be centered approximately between four adjacent sprinklers.
• The vertical distance from the fan to the sprinkler deflector must be at least 3 ft (91.4 cm).
• The fan must be interlocked to shut down immediately upon receiving a waterflow signal from the alarm
system.
The fire relay is provided for fans that will be installed in buildings that have a fire sprinkler system. The fire relay
integrates the fan with the sprinkler system and shuts down the fan upon receiving an alarm signal from the
system. Note: In the configuration shown, power must be applied to the fire relay to enable fan operation.
Controller Input Cable
White
+0–10 VDC Speed Ref.
Brown
Not Used
Orange
Status LED (+)
Yellow
Run Enable
Closed: Enable; Open: Disable
Blue
Green
Status LED (-)
Red
+10 VDC Supply
Black
DC Common
Controller
Input Cable
Wall Controller
WWW.BIGASSSOLUTIONS.COM
© 2015 DELTA T CORP.
RED
WHITE
YELLOW
ORANGE
BLUE
YELLOW
BLUE
CAT5 Cable
ALL RIGHTS RESERVED.
From main FACP
or NAC box, if
applicable
RED
WHITE
Relay Coil/Contact Details
White (X2) (-)
C Blue
NC Yellow
Red (X2)
(+)
NO Orange
Coil: 20–32 VDC @ 20 mA
To wall
controller
23