4.5. CONDENSATE AVENT P190/P310/P460
1
1
1. Fasten condensate line (1) using a hose clip and clip in a
loop in a funnel or a siphon.
Observe a condensate discharge depth (A) of at least
100 mm.
Note:
When converting the room ventilation unit to the right
version (B), the blind cover of the condensate connector
must be exchanged.
2. Fill water into the condensate pan and check proper
draining of the water.
16
OII Avent P190/P310/P460
A
A
M+P-26A-0843
4.6. COMMISSIONING
4.6.1.
Control unit
3
4
1
8
9
10
11
12
13
1
Main board
2
Control unit
3
230 V electrical connection
4
Digital input for accessories (HAC1)
5
Antenna for radio remote control (accessory)
6
Modbus connection (BMS connection)
Connector configuration RS 485
7
Access LAN connection (router)
Connector configuration RJ45 TCP/IP
8
USB port for service work
9
Switching on/off summer mode or bypass
10 Setting ventilator levels
11 Displaying the ventilator levels
12 Selecting weekly programme or need-based
programme
13 Reset filter alarm
Error display
5
6
7
2